Capacity: how many metrics fit
For users installing many Modbus devices on one Sentinel. The figures come from computer simulation with the same payload-building code as the firmware; they have not been measured on a real board and broker. Firmware 0.20.
The real limits
Section titled “The real limits”| Limit | Value | Consequence if exceeded |
|---|---|---|
| Telemetry message length | 12,086 B | the message is not sent; the oversize_dropped counter rises (web: Memory card; serial log) |
| Length of one history sample (when MQTT is down, direct mode) | 10,238 B | the sample is skipped from history |
| Number of source metrics | 400 | a source that exceeds the limit is rejected |
| Number of sources | 40 | the next source is rejected |
| Registers (metrics) per source | 16 | the source is rejected |
sources message |
6144 B | the whole message is rejected, the old set keeps running |
What binds in practice is message length, not the number of metrics: with long names the message is full before 400 metrics are reached.
Rough formula
Section titled “Rough formula”Telemetry size ≈ base + number of metrics × (name length + 9 to 12) bytes. Base = the board’s built-in metrics, ±940 B on G1 (all sensors active). Name length is the full <prefix>_<suffix> name (e.g. rak3_voltage = 12). 9 applies to plausible values (voltage, current, power); 12 to all values being 9-character numbers.
Maximum number of metrics per name length (SNT-G1)
Section titled “Maximum number of metrics per name length (SNT-G1)”| Name length | Plausible values | Worst-case values | History |
|---|---|---|---|
| 6 | 734 | 619 | 613 |
| 8 | 649 | 557 | 541 |
| 10 | 581 | 506 | 485 |
| 12 | 526 | 464 | 439 |
| 16 | 442 | 398 | 369 |
| 20 | 382 | 348 | 318 |
| 24 | 336 | 309 | 280 |
“History” uses the 10,238 B sample limit: that is the limit when MQTT is down and history is active. Example: 40 SDM120 with prefixes m1…m40 (names ±11 characters, 400 metrics) fit with margin; 40 SDM120 with 12-character prefixes (names of 20 to 22) are no longer safe on G1.
Rules for users
Section titled “Rules for users”- Use short names. Source prefixes of 2 to 6 characters (
m1,rak3,pz2); the profile suffix already adds 3 to 8 characters. - Install only the metrics you need. A compact profile (SDM120: voltage, current, power, energy = 4 metrics, not 10) shrinks the message and speeds up the read cycle.
- Measure before installing. After the set is loaded, look at
oversize_droppedin the web Status tab orGET /api/status; it must stay 0. - Use telemetry groups so rarely-changing values are sent less often and messages are smaller.