Digital inputs

Four dry-contact inputs. The pin of each slot is fixed: d1 GPIO16, d2 GPIO38, d3 GPIO48 (through the UPS optocoupler), d4 GPIO15. Connect one contact wire to the pin and the other to GND; the pull-up is built in.

All inputs are off by default (dN_type = off): the node does not know whether a pin is connected, so it does not read and does not send anything until you configure it.

Key Default Function
dN_type off off, door, ups, water, smoke, generic. The type only determines the default LCD status text
dN_active high the pin level that means active (value true). high if an open contact = active; low if a contact closing to GND = active
dN_name empty metric name (front_door). Empty = slot ID
dN_label D1… name for the LCD, max. 11 characters
dN_text_true, dN_text_false empty LCD status text, max. 8 characters. Empty = type default
dN_alarm false true = this input may trigger an alarm
dN_alarm_on active the alarm fires when the input is active, or when it is inactive (e.g. cable unplugged)
dN_alarm_delay_s -1 how long the condition must persist. -1 = follow alarm_delay_s; 0 = immediate

Default LCD status text (shown on the LCD in Indonesian):

Type Active Inactive
door BUKA (open) TUTUP (closed)
ups BATERAI (battery) ONLINE
water BOCOR (leak) KERING (dry)
smoke ASAP (smoke) AMAN (safe)
generic AKTIF (active) NORMAL

The value sent to the server is always a boolean on the metric dN_name (true = active according to dN_active).

Door with an MC-38 reed switch (magnet attached = contact closed = pin LOW; door open = HIGH):

{"cfg_ver":5,
"d1_name":"front_door","d1_type":"door","d1_active":"high","d1_label":"Pintu Depan",
"d1_text_true":"Terbuka","d1_text_false":"Tertutup","d1_alarm":true,"d1_alarm_delay_s":20}

The alarm only fires if the door stays open for more than 20 seconds, so a door opened briefly does not sound.

UPS (“on battery” dry contact through a PC817 to d3; opto on = pin LOW):

{"cfg_ver":6,
"d3_name":"ups_on_battery","d3_type":"ups","d3_active":"low","d3_label":"UPS","d3_alarm":true,"d3_alarm_delay_s":10}

Water leak sensor (dry contact):

{"cfg_ver":7,
"d4_name":"water_leak","d4_type":"water","d4_active":"low","d4_label":"Bocor","d4_alarm":true,"d4_alarm_delay_s":0}

Smoke detector:

{"cfg_ver":8,
"d4_name":"smoke_detector","d4_type":"smoke","d4_active":"high","d4_label":"Asap","d4_alarm":true,"d4_alarm_delay_s":0}

Generic contact input: {"d2_name":"panel_door","d2_type":"generic","d2_active":"low","d2_label":"Panel"}; add d2_alarm if needed.

For sensors whose failure is dangerous (smoke, UPS), use an NC contact and make the alarm fire when the input is inactive:

{"cfg_ver":9,"d4_alarm_on":"inactive"}

The alarm is then named alarm_smoke_detector_inactive.

Trigger the sensor, then look at status in serial: "din":{"front_door":true} means active. On the LCD, the Input page shows the label and status text; the web Status tab shows the same. An input of type off appears nowhere.

A change in input state is sent as an event immediately, in addition to its value in the regular telemetry.