Alarms

Sentinel evaluates alarms itself, so the buzzer and LCD on site keep working when the WAN is down. The limits are set from the server or the web; every status change is sent as an event, and the current status accompanies the telemetry.

What can trigger an alarm: temperature (each slot), power (PZEM-004T), and digital inputs with dN_alarm = true. Other inputs (e.g. a door without dN_alarm) are only reported and displayed. For other metrics (Modbus meters, humidity) use rules.

All take effect immediately without a reboot. A limit of 0 = that alarm is disabled.

Key Default Range Meaning
temp_warn_c 30 0 … 125 default warning for all temperature slots. Must be lower than temp_alarm_c
temp_alarm_c 35 0 … 125 default alarm for all temperature slots
temp_alarm_hyst_c 1 0 … 10 a temperature alarm ends after the temperature drops this far below the limit
alarm_delay_s 30 0 … 3600 the condition must persist this long before the alarm becomes active (all alarms)
volt_min_v, volt_max_v 0 0 … 300 low and high voltage limits
current_max_a 0 0 … 100 overcurrent
power_max_w 0 0 … 25000 overpower
alarm_buzzer true buzzer sounds on alarm (not on warning)
maintenance_until 0 epoch seconds maintenance mode until this time

Per-slot limits (tN_warn_c, tN_alarm_c) and per-input delays (dN_alarm_delay_s) override these defaults. The effective warning must be lower than the effective alarm for each slot.

  • Delay. An alarm becomes active after the condition persists for alarm_delay_s (digital input: dN_alarm_delay_s, or alarm_delay_s if -1). Shorter spikes are ignored.
  • Hysteresis. An alarm ends once the value returns past the limit by the hysteresis: temp_alarm_hyst_c for temperature, 2% of the limit for power. Ending does not use a delay.
  • An unreadable sensor does not change alarm status: an active alarm stays active until the sensor is readable again.
  • Two temperature levels. Warning (alarm_<name>_warn) and alarm (alarm_<name>_high) are two separate alarms; a temperature rising past both produces two events.
  • Combined level alarm_level: 0 = normal, 1 = a warning exists, 2 = an alarm exists.
  • Changing a limit while an alarm is active re-evaluates it; if the condition ended, an end event is sent. Disabling an alarm (0) while active also sends an end event once.

Names follow alarm_<name>_<condition>, where <name> = the slot metric name (tN_name, dN_name; slot ID if empty).

Alarm Status metric Trigger value Level
Temperature warm alarm_<name>_warn …_warn_value (Cel) warning
Temperature high alarm_<name>_high …_high_value (Cel) alarm
Input active alarm_<name>_active none alarm
Input inactive alarm_<name>_inactive none alarm
Voltage low / high alarm_voltage_low, alarm_voltage_high …_value (V) alarm
Overcurrent alarm_current_high …_value (A) alarm
Overpower alarm_power_draw_high …_value (W) alarm
  • An alarm makes the LCD bottom line blink and the buzzer sound a pattern of four short beeps (80 ms on, 80 ms off) then 440 ms of silence, repeating every second. A warning only appears as text.
  • BACK silences the alarms active at that moment (sound stops, no event is emitted). A new alarm, or an alarm that ended and became active again, makes the buzzer sound again and the screen jumps to the Summary.
  • alarm_buzzer = false or maintenance mode silences the buzzer; events and status are still sent.

maintenance_until (epoch seconds) silences the buzzer until that time, and telemetry carries maintenance: true. Alarm events are still sent, so the server can flag data during maintenance. It needs the node clock to be synchronized (NTP). A maintenance event is emitted at start and end.

Situation Behavior
Node reboots while an alarm is active no end event. After boot and the delay, a start event is sent again; treat it as an update, not a new incident
MQTT down when status changes the event is held and sent once connected; the last status is sent, not every change in between
Node clock not synchronized events are sent without their own time; the server uses receive time. Maintenance mode is inactive
Slot name changed while an alarm is active the node first sends an end event for the old alarm name