Configuration keys

All keys can be sent from the server (…/<mac>/config, retained JSON), from the web interface (Configuration tab), or over USB serial as one JSON line. N = slot number. Keys marked reboot make the node restart about 1 second after being applied; otherwise they take effect immediately. How cfg_ver, rejected, and the retained rules work is in Config and reports.

Key Type Default Notes
mqtt_host text, max. 63 auto auto = gateway IP from DHCP. reboot
mqtt_mode enum auto auto, mqtt3, mqtt5, mqtts3, mqtts5 (Network and connection modes). reboot
mqtt_port integer 0 … 65535 0 non-TLS port; 0 = the type’s default (11883 / 11884). reboot
mqtts_port integer 0 … 65535 0 TLS port; 0 = 18883. reboot
mqtt_ca PEM text, max. 3000 empty private CA for TLS, replacing the public bundle. Its value is not in the report, only its summary. reboot
ntp_server text, max. 63 auto NTP server. Effective list in ntp_server_effective. reboot
workspace, channel text, max. 64 empty both filled = direct mode. reboot
mqtt_user, mqtt_pass text, max. 64 / 128 empty direct mode: device ID and device key. mqtt_pass is write-only. reboot
label text, max. 20 empty location name on the LCD
hw text, max. 8 A hardware revision, set during assembly
Key Type Default Range Notes
payload_format text flat2 (new units) flat, senml, flat2 payload format (Payload formats). reboot
telemetry_interval_ms integer 10000 5000 … 3600000 regular send interval
temp_report_delta_c decimal 0.5 0 … 20 send early if a slot’s temperature changes by this much; 0 = disabled
power_report_delta_w decimal 10 0 … 5000 send early if power changes by this many watts (absolute); 0 = disabled
hist_kb integer 2048 0 … 6144 history buffer in PSRAM (KiB), direct mode only with flat2. 0 = disabled. hist_effective_kb in the report = the size actually active. reboot

Telemetry is also sent early when the alarm level changes and when a sensor disappears or returns; the minimum gap between sends is 2 seconds.

Key Type Default Notes
pzem boolean true the PZEM-004T is read and power metrics are sent
sht41 boolean false SHT41 installed. reboot
temp_autobind boolean true a new DS18B20 is automatically bound to the lowest empty temperature slot
Key Type Default Range Notes
tN_en boolean true false turns the slot off
tN_label text T1… max. 12 ASCII name for humans and the LCD
tN_name text empty [a-z][a-z0-9_], max. 24 metric name; empty = slot ID
tN_rom text empty 16 hex starting with 28 the ROM of the bound sensor
tN_offset_c decimal 0 −10 … 10 calibration
tN_warn_c, tN_alarm_c decimal -1 −1 … 125 per-slot limits; -1 = follow default, 0 = disabled
Key Type Default Range Notes
dN_type text off off, door, ups, water, smoke, generic
dN_active text high high, low the pin level that means active
dN_name text empty like tN_name metric name
dN_label text D1… max. 11 ASCII
dN_text_true, dN_text_false text empty max. 8 ASCII LCD status text
dN_alarm boolean false may trigger an alarm
dN_alarm_on text active active, inactive
dN_alarm_delay_s integer -1 −1 … 3600 -1 = follow alarm_delay_s
Key Type Default Notes
oN_en boolean false slot enabled
oN_active text low high / low: the pin level that means ON
oN_label text O1… max. 11 ASCII
oN_name text empty metric name
Key Type Default Range Notes
temp_warn_c decimal 30 0 … 125 default temperature warning; must be < temp_alarm_c
temp_alarm_c decimal 35 0 … 125 default temperature alarm
temp_alarm_hyst_c decimal 1 0 … 10 temperature hysteresis
alarm_delay_s integer 30 0 … 3600 delay for all alarms
volt_min_v, volt_max_v decimal 0 0 … 300 volt_min_v < volt_max_v
current_max_a decimal 0 0 … 100
power_max_w decimal 0 0 … 25000
alarm_buzzer boolean true buzzer on alarm
maintenance_until integer 0 epoch seconds maintenance mode; needs a synchronized clock
Key Type Default Range Notes
lcd boolean true LCD installed. reboot
lcd_backlight_s integer 120 0 … 3600 0 = always on
lcd_idle_s integer 60 0 … 3600 return to the Summary; 0 = never
tz_offset_min integer 420 −720 … 840 time zone of the LCD clock and rule schedules
buttons_locked boolean false the Actions item in the LCD menu is disabled
exp_addr integer 33 (0x21) 32 … 39 or 56 … 63 PCF8574 I2C address. reboot
lcd_addr integer 0 0 or like exp_addr 0 = automatic; must not equal exp_addr. reboot
Key Type Notes
fw_version text target version; empty = no target
fw_url text .bin address; starting with / = from the gateway
fw_sha256 text the file’s SHA-256, 64 hex

Details: Firmware and OTA.

Apply to tN_name, dN_name, oN_name, and Modbus source metric names:

  • lowercase letters, digits, _; starts with a letter; max. 24 characters;
  • unique across all slots (an empty name counts as the slot ID); swapping the names of two slots in one message is allowed;
  • must not start with alarm_, rule_, flag_, src_, and must not be a fixed name: voltage, current, power_draw, energy, frequency, power_factor, temp_ambient, humidity, maintenance, uptime, heap_free, state, fw, model, hw, ip, gateway, button;
  • renaming starts a new data series; moving a name to another slot does not.