Metrics

Metric names are lowercase with digits and _. The following names are sent in telemetry, event, and status (Payload formats). A sensor that cannot be read is not sent.

Metric Type Unit Source
tN_name (default t1…t4) number Cel DS18B20 per active slot
temp_ambient number Cel SHT41
humidity number %RH SHT41
voltage number V PZEM-004T
current number A PZEM-004T
power_draw number W PZEM-004T
energy number kWh PZEM-004T (cumulative)
frequency number Hz PZEM-004T
power_factor number / PZEM-004T
dN_name (default d1…d4) boolean digital input (true = active)
oN_name (default o1…o4) boolean digital output (true = ON)
uptime number s ESP32
heap_free number By ESP32
expander_ok boolean false = PCF8574 not answering
maintenance boolean only while maintenance mode is active
Metric Meaning
alarm_level 0 normal, 1 warning, 2 alarm
alarm_<name>_warn, alarm_<name>_high temperature warning and alarm of slot <name>; trigger value in …_value
alarm_<name>_active, alarm_<name>_inactive digital input alarms
alarm_voltage_low, alarm_voltage_high, alarm_current_high, alarm_power_draw_high power alarms; trigger value in …_value

See Alarms.

Metric Meaning
rule_<id> active status of each rule with en: true (boolean); rule_<id>_value if an event action uses val
flag_f1…flag_f4 flags used by the rules set
src_<id>_ok Modbus source diagnostics (only if diag: true)
prefix_suffix Modbus device metrics, e.g. rak1_voltage, grid_power

state (online / offline), fw, model, hw, ip, gateway, and button (button events: identify, factory_reset).

alarm_, rule_, flag_, and src_ must not be used as the prefix of a slot or source name.